boiler_sensors.gifBoiler temperature sensors 91076, 91077 and 91075 boiler_sensors.gifThe temperature sensors 91076 and 91077 are used for our boiler control systems 95016, 95025, 95035, 95037, 95055, 95060, 95090, 95092, 96100-96105

Resistance table 91076/91077
°C Ohm ±5%
----- -------------
20 2500
25 2000
30 1610
40 1065
50 720
60 497
70 350
80 251
90 183
100 136
110 102
120 78

 

The temperature sensor 91075 is used for our boiler control systems 91282, 95001, 95010, 95012, 95070, 95110, 95120, 95121, 95140, 95170, 95172.

Resistance table 91075

°C Ohm ±5%
----- -------------
20 2750
25 2200
30 1775
40 1175
50 794
60 548
70 386
80 277
90 201
100 149
110 112
120 85

 

 